§ 5704-02 Precision Testing of Certain Underground Storage Systems.
RCNY § 5704-02
(a)Scope. This section sets forth standards, requirements and procedures for precision testing pursuant to FC 5704.2.11.6 of underground storage systems for motor fuels or other flammable and combustible liquids when such systems utilize single-walled tanks, or other tanks not provided with a leak detection system meeting Fire Code requirements.
(b)General Provisions.
(1)Applicability. Precision testing of underground storage systems for motor fuels or other flammable and combustible liquids that utilize single-walled tanks, or other tanks not provided with a leak detection system meeting Fire Code requirements, shall be conducted in compliance with the requirements of FC Chapters 23 and 57 and this section.
(2)Precision testing standard. Precision testing of underground storage systems shall be conducted in accordance with National Fire Protection Association (NFPA) Standard 329 (2005 edition).
(3)Supervision. (A) Certificate requirements. Precision testing of underground storage systems shall be conducted by a person holding a certificate of license or under the general supervision of a certificate of license holder. Such person shall be trained and knowledgeable in the use of the precision test equipment and procedures for the conduct of the particular precision test. Any person conducting such test under the supervision of a certificate of license holder shall hold a certificate of fitness for such precision test. A separate certificate of fitness shall be obtained for each type of precision test system. (B) Presence on premises. The certificate holder conducting the precision test shall remain on the premises while such test is being conducted and until the system has been returned to good working order in accordance with 3 RCNY § 5704-02(c)(1)(C).
(c)Operational Requirements.
(d)Portable Fire Extinguisher Requirements.