Brooklyn since 2014All five boroughsSame-day response during business hours

What is NYC MC § 607.3.3.2?

Quick Answer

This section outlines the requirements for smoke damper actuation in buildings, specifying the installation of smoke detectors in relation to smoke dampers. It details various installation scenarios, including ducted and unducted systems, and the necessary proximity of detectors to dampers. Applies to building owners responsible for fire safety systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

607.3.3.2 Smoke damper actuation.

MC § 607.3.3.2

The smoke damper shall close upon actuation of a listed smoke detector or detectors installed in accordance with Section 606 of this code and Section 907.3 of the New York City Building Code and one of the following methods, as applicable: 1. Where a smoke damper is installed within a duct, a smoke detector shall be installed inside the duct or outside the duct with sampling tubes protruding into the duct. The detector or tubes within the duct shall be within 5 feet (1524 mm) of the damper. Air outlets and inlets shall not be located between the detector or tubes and the damper. The detector shall be listed for the air velocity, temperature and humidity anticipated at the point where it is installed. Other than in mechanical smoke control systems, dampers shall be closed upon fan shutdown where local smoke detectors require a minimum velocity to operate. Exception: Duct smoke detectors will not be required at each smoke or combination fire smoke damper provided: 1. The supply fan shall shut down and all the smoke and combination fire smoke dampers associated with the supply system automatically close upon actuation of any automatic alarm initiating device on the floor(s).

2.Nonducted return air systems shall have a smoke detector located within 5 feet (1.5 m) upstream of each return air or transfer opening in a fire barrier rated 2-hour or greater.

3.Ducted return air systems shall have a duct smoke detector located within 5 feet (1.5 m) of a smoke damper; additional smoke detectors are not required at smoke and combination fire smoke dampers located downstream where there are no additional return air inlets.

4.Where a smoke damper is installed in a corridor wall or ceiling, the damper shall be permitted to be controlled by a smoke detection system installed in the corridor.

5.Where a smoke detection system is installed in all areas served by the duct in which the damper will be located, the smoke dampers shall be permitted to be controlled by the smoke detection system.

6.Smoke dampers that are part of an engineered smoke control system shall be capable of being positioned manually from a command station. Such positioning devices shall be provided for supply and return/exhaust dampers grouped by floor and by type. Damper switch positions shall indicate whether the related dampers are commanded to be either open or closed. Smoke damper positioning switches shall be located at the Fire Command Station, or in a Mechanical Control Center in buildings without a Fire Command Station.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 607.3.3.2?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters