618.2 Forced-air furnaces.
FGC § 618.2
The minimum unobstructed total area of outdoor and return air ducts or openings to a forced-air warm-air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer's instructions. The minimum unobstructed total area of supply ducts from a forced-air warm-air furnace shall be not less than 2 square inches (1290.32 mm 2 ) for each 1,000 Btu/h (4402 mm 2 /W) output rating capacity of the furnace and not less than that specified in the furnace manufacturer's instructions. Exception: The total area of supply air ducts and outdoor and return air ducts shall not be required to be larger than the minimum size required by the furnace manufacturer's instructions.













