This section outlines the requirements for exhaust ventilation systems, including installation standards, continuous operation, manual shutoff controls, and specific design considerations based on the density of fumes or vapors. The statute aims to ensure safety in environments where hazardous materials are stored. Applies to building owners managing facilities with such systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

502.8.1.1 System requirements.

MC § 502.8.1.1

Exhaust ventilation systems shall comply with all of the following: 1. The installation shall be in accordance with this code.

2.Mechanical ventilation shall be provided at a rate of not less than 1 cfm/ft 2 (0.00508 m 3 /(s • m 2 )) of floor area over the storage area.

3.The systems shall operate continuously unless alternate designs are approved.

4.A manual shutoff control shall be provided outside of the room in a position adjacent to the access door to the room or in another approved location. The switch shall be a break-glass or other approved type and shall be labeled: VENTILATION SYSTEM EMERGENCY SHUTOFF.

5.The exhaust ventilation shall be designed to consider the density of the potential fumes or vapors released. For fumes or vapors that are heavier than air, exhaust shall be taken from a point within 12 inches (304.8 mm) of the floor. For fumes or vapors that are lighter than air, exhaust shall be taken from a point within 12 inches (304.8 mm) of the highest point of the room.

6.The location of both the exhaust and inlet air openings shall be designed to provide air movement across all portions of the floor or room to prevent the accumulation of vapors.

7.The exhaust air shall not be recirculated to occupied areas if the materials stored are capable of emitting hazardous vapors and contaminants have not been removed. Air contaminated with explosive or flammable vapors, fumes or dusts; flammable, highly toxic or toxic gases; or radioactive materials shall not be recirculated.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 502.8.1.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters