Brooklyn since 2014All five boroughsSame-day response during business hours

What is NYC MC § 1107.2.1?

Quick Answer

This section prohibits the installation of refrigerant piping in public corridors, with specific exceptions for Group A1 refrigerants under certain conditions. These conditions include limitations on refrigerant density and requirements for safety features such as shutoff valves and alarms. Applies to building owners managing refrigerant systems in public spaces.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1107.2.1 Piping in public corridors.

MC § 1107.2.1

Refrigerant piping shall not be installed in public corridors. Exception: Refrigerant piping in public corridors that complies with either of the following conditions: 1. Piping containing Group A1 refrigerant may be located in public corridors provided that the complete discharge of any one refrigerant system into the public corridor will not result in a refrigerant density equal to or greater than 50 percent of the allowable density set forth in Table 1103.1; and 1.1. There is not more than one refrigerant system's piping per tenant; and 1.2. Refrigerant piping and fittings are concealed or otherwise protected from mechanical damage; and either 1.3. Refrigerant piping and fittings are installed with brazed joints; or 1.4. The refrigerant equipment manufacturer provided pre-charged tubing systems installed in accordance with the refrigerant equipment manufacturer's instructions; 2. Piping containing Group A1 refrigerant may be located in public corridors provided that the complete discharge of any one refrigerant system into the public corridor will not result in a refrigerant density of 100 percent of the allowable refrigerant density set forth in Table 1103.1; and 2.1. Such system is provided with fast-acting shutoff valves on both high and low pressure refrigerant line sets, actuated by either local refrigerant monitors in the corridor, or on sensing a drop in pressure on either high or low pressure refrigerant line sets; and 2.2. Upon accidental discharge, actuation of installed refrigerant shutoff valves shall initiate locally installed alarm; and 2.3. Installation of fast-acting shutoff valves, refrigerant detectors, and alarms shall be in accordance with Appendix C; and 2.4. There is not more than one refrigerant system's piping per tenant; and 2.5. Refrigerant piping and fittings are concealed or otherwise protected from mechanical damage; and either 2.6. Refrigerant piping and fittings are installed with brazed joints; or 2.7. The refrigerant equipment manufacturer provided pre-charged tubing systems installed in accordance with the refrigerant equipment manufacturer's instructions.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1107.2.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters