503.8 Venting system termination location.
FGC § 503.8
The location of venting system terminations shall comply with the following: 1. Gas venting systems shall be extended at least 3 feet (914.4 mm) above the highest construction, such as a roof ridge, parapet wall, or penthouse, within 10 feet (3048 mm) of the vent outlet whether the construction is on the same building as the chimney or on another building. However, such constructions do not include chimneys or other vents, or open structural framing. The vent shall be as high as such construction which is located beyond 10 feet (3048 mm) from the vent and up to and including the distance determined by Equation 5-2. Exception: Horizontally terminated direct-vent appliances and integral vent appliances approved by the commissioner and installed in accordance with the manufacturer's instructions and Section 503.8 Item 3.
2.Where permitted, through-the-wall vents for Category I, II, III and IV appliances and noncategorized condensing appliances shall not terminate over public walkways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equipment.
3.Horizontal terminations shall only be allowed if they are in a nonhazardous location and if the appliance has a sealed combustion chamber (direct vent) or integral vent in accordance with the appliance listing and manufacturer's instructions. In addition, horizontal terminations shall comply with the following requirements: 3.1. Where located adjacent to walkways, the termination shall be not less than 7 feet (2133.6 mm) above the level of the walkway. 3.2. Vents shall terminate at least 3 feet (914.4 mm) above any forced air inlet, other than the forced air inlet for the subject direct vent or integral vent appliance, located within 10 feet (3048 mm). 3.3. The vent system shall terminate at least 4 feet (1219.2 mm) below, 4 feet (1219.2 mm) horizontally from or 1 foot (304.8 mm) above any door, window or gravity air inlet into the building. 3.4. The vent termination point shall not be located closer than 3 feet (914.4 mm) to an interior corner formed by two walls perpendicular to each other. 3.5. The vent termination shall not be mounted directly above or within 3 feet (914.4 mm) horizontally from any gas or electric metering, regulating, venting relief equipment or other building opening. 3.6. The bottom of the vent termination shall be located at least 36 inches (914.4 mm) above finished grade. 3.7. The maximum heat input of an appliance served by single horizontal vent termination shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 3.8. The maximum heat input of all appliances served by horizontal vent terminations located within a 10 feet (3048 mm) radius shall be 350,000 Btu/h (102.6 kW), unless otherwise approved by the commissioner. 3.9. The vent termination shall be located a minimum of 4 feet (1219.2 mm) from the lot line or from adjacent buildings. The termination shall be installed in accordance with the gas vent manufacturer's listing and instructions. (Am. L.L. 2023/077, 6/11/2023, eff. 6/11/2023) Editor's note: For related unconsolidated provisions, see Appendix A at L.L. 2023/077.













