This section outlines smoke control requirements for buildings classified in specific occupancy groups, detailing ventilation system interconnections, smoke detection in public areas, and mechanical exhaust systems. The statute emphasizes safety measures to prevent smoke spread and ensure effective ventilation. Applies to building owners of classified occupancy group C, D, E, F, G, H, J-1, or J-2.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

§ 27-777.1 Smoke control requirements.

AC § 27-777.1

(a)In all buildings classified in occupancy group C, D, E, F, G, H, J-1 or J-2: (1) Ventilation systems supplying different occupancy groups shall not be interconnected, provided however that a ventilation system may serve two occupancy groups located on the same floor when the accessory use occupies less than twenty per cent of the floor area occupied by the principal use.

(2)Ventilation systems supplying corridors shall not be interconnected with systems serving other spaces, except that this requirement shall not apply to floors used exclusively as office space in buildings classified in occupancy group E which are fully sprinklered.

(3)A ventilation system supplying any part of a means of egress shall not be interconnected with any other ventilation system.

(4)A ventilation system supplying public areas and assembly spaces shall have smoke detecting devices that will shut down the system upon detecting smoke.

(5)In buildings classified in occupancy group J-2, ventilation systems supplying individual apartments shall not be directly connected with any other ventilation system.

(6)Except in buildings classified in occupancy group J-2, and as otherwise provided in section 27-343 of article five of subchapter five of this chapter, either a combined heat and smoke damper or independent heat and smoke dampers shall be installed at any penetration of construction required to have a fire-resistance rating.

(b)In all buildings classified in occupancy group C, D, E, F, G, H or J-1, there shall be provided a system of mechanical means of sufficient capacity to exhaust six air changes per hour or 1 cfm/sq. ft., whichever is greater, from the largest floor in the building, using either dedicated fan equipment or the building ventilation system arranged to shut down automatically with manual override capability to exhaust one floor at a time through a roof or an approved location on an exterior wall other than a lot line wall.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 27-777.1?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters