This section outlines ventilation requirements for school buildings, specifying air supply and exhaust standards for classrooms, administrative rooms, and assembly areas. It mandates a minimum supply of outdoor air per occupant and mechanical exhaust specifications. Applies to school building owners and operators responsible for maintaining proper ventilation systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

§ 27-765 Ventilation for schools.

AC § 27-765

School buildings shall be ventilated in accordance with the following requirements: (a) Rooms of instruction and administration. Classrooms, other rooms of instruction, and administrative rooms, where the index for ventilation is less than one thousand six hundred fifty, shall have a supply of outdoor air of at least fifteen cfm per occupant and mechanical exhaust. Where windows are used as the source of supply air, mechanical air exhaust shall be fifteen cfm per occupant. When outdoor air is supplied by mechanical means, the exhaust shall be at least eighty per cent of the supply. In air-conditioned rooms, the conditioned air supply may be reduced to a minimum of ten cfm per occupant, of which at least five cfm shall be outdoor air.

(b)Lockers and wardrobes. Lockers, wardrobes, or wardrobe rooms shall be ventilated in accordance with the provisions of section 27-760 of this article, and where these spaces are located within or adjacent to classroom, the exhaust air from the classroom may be used for such ventilation.

(c)Auditoria and assembly rooms. Rooms where there are more than seventy-five occupants shall have a supply of outdoor air of at least fifteen cfm per occupant and mechanical exhaust. Where windows are used as the source of supply air, mechanical air exhaust shall be at least fifteen cfm per occupant. When outdoor air is supplied by mechanical means, the mechanical exhaust shall be at least eighty per cent of the supply. In air-conditioning spaces, the conditioned air supply may be reduced to a minimum of ten cfm per occupant, of which at least five cfm shall be outdoor air.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 27-765?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters