This section establishes the minimum outdoor air supply requirements for mechanical ventilation in occupiable rooms, specifying different standards based on room type and conditions. The Department of Buildings enforces these regulations, which apply to building owners managing mechanical ventilation systems in their properties.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

§ 27-754 Minimum quantity of outside air for mechanical ventilation.

AC § 27-754

The minimum quantity of outside air required for mechanical ventilation in any occupiable room, where not otherwise prescribed, shall be determined according to table 12-2. TABLE 12-2Required Minimum Outdoor Air Supply and Exhaust(cfm per sq. ft.) Index for VentilationVentilated Rooms with Natural Ventilation OpeningsVentilated Rooms without Natural Ventilation OpeningsAir Conditioned RoomsSupplyExhaustSupplyExhaustSupplyExhaust0- 3002.52.02.52.01.51.5301- 5202.01.52.01.51.21.2521- 8501.51.25 1.51.250.90.9851-1250-1.01.0 1.0 0.6 0.6 1251-1650-0.670.670.670.5 0.5 over 1650 - -0.33 0.33 0.4 0.4 (a) Window requirements. To be credited as ventilating openings under the provisions of this subchapter, windows or other openings shall meet the requirements of section 27-749 of article six of this subchapter, and where mechanical supply ventilation is not provided, shall have a free openable area of at least one square foot per one hundred square feet of floor area.

(b)Air conditioning.

(1)In air conditioned rooms, the windows and other openings shall not be credited as such in computing the index for ventilation. Air conditioned rooms shall be considered as interior rooms.

(2)Air that has been exhausted from an air conditioned space may be reconditioned by air conditioning apparatus and recirculated as equivalent outdoor air, provided that the total of supply air is not less than required for air conditioned rooms by table 12-2 and that the amount of actual outdoor air is at least thirty-three and one-third per cent of the required total. The actual outdoor air supply shall not, under any circumstances, be reduced to less than five cfm per occupant, except that these minimum requirements may be reduced by fifty per cent as provided in section 27-755 of this article.

(c)Required exhaust. Required exhaust may be accomplished by raising the pressure within the space with consequent leakage through doors and windows, or by drawing the vitiated air from air conditioned spaces into the return air duct of air conditioning apparatus or into an exhaust duct discharging directly to the outdoor air.

(d)Make-up air. A sufficient quantity of air to make the exhaust system effective shall be provided to the space being exhausted by one or by any combination of the following methods: (1) By supplying air to the space by means of a blower system.

(3)By infiltration through cracks around window sash and doors.

(4)By other methods acceptable to the commissioner.

(e)Prohibited use of recirculated air. Air drawn from any of the following spaces may not be recirculated; mortuary rooms; bathrooms or toilet rooms; or any space where an objectionable quantity of flammable vapors, dust, odors, or noxious gases is present. Air drawn from rooms that must be isolated to prevent the spread of infection shall not be recirculated, except that air drawn from hospital operating rooms may be recirculated, if in compliance with the following requirements: (1) There shall be a minimum of twenty-five total air changes per hour, of which five air changes per hour shall be outdoor air.

(5)All ventilation or air conditioning systems serving such rooms shall be equipped with a filter bed of twenty-five per cent efficiency upstream of the air conditioning equipment and a filter bed of ninety per cent efficiency downstream of the supply fan, any recirculating spray water systems and water reservoir type humidifiers. All filter efficiencies shall be average atmospheric dust spot efficiencies tested in accordance with ASHRAE standard 52-68.

(6)A manometer shall be installed across each filter bed.

(7)Duct linings shall not be used in ventilation and air conditioning systems serving such rooms unless terminal filters of at least ninety per cent efficiency are installed downstream of linings.

(8)Air supplied shall be delivered at or near the ceilings and all exhaust air shall be removed near floor level, with at least two exhaust outlets not less than three inches above the floor.

(f)Outdoor air intakes. For high-rise office buildings erected pursuant to new building applications filed on or after the effective date of this section, outdoor air intakes serving spaces above the second story and serving spaces greater than ten thousand square feet of floor area shall be located at least twenty feet above ground level, at least twenty feet from exhaust outlets of ventilation systems and other exhaust discharges, and at least twenty feet from areas that may collect vehicular exhaust such as off-street loading bays.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 27-754?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters