What is NYC FC § 609.6.2?

Quick Answer

This section mandates that a visual inspection of commercial cooking fire extinguishing systems be conducted monthly by a trained individual. The inspection must confirm the system's integrity and operational status, including checks on the extinguishing agent and accessibility of activation devices. Applies to owners of commercial cooking establishments with such systems.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

609.6.2 Periodic inspection.

FC § 609.6.2

A visual inspection of a commercial cooking fire extinguishing system shall be conducted at least once a month by a trained and knowledgeable person in accordance with FC 904.5.1 to confirm that the system appears to be in good working order, including the following conditions: 1. The fire extinguishing system is intact and undamaged, including the extinguishing agent container, system piping, nozzles and protective nozzle caps.

2.The fire extinguishing system is charged and operational. Check the pressure gauge and/or control head (on a wet chemical system) to confirm that system is operational and the extinguishing agent has not been discharged. On other systems monitored by a fire alarm system, check the fire alarm system control panel to confirm that there are no supervisory or trouble signals.

3.The fusible links or other heat detection devices are not coated with grease.

4.Any movable commercial cooking appliances are in position under the proper fire extinguishing system nozzle, in accordance with approved floor markings, so that the nozzles are centered over the commercial cooking appliance.

5.Access to the manual activation device for the commercial cooking fire extinguishing system is not obstructed and the tamper indicator is intact.

6.The maintenance tag is in place for the commercial cooking fire extinguishing system and has not expired.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 609.6.2?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters