This section outlines the conditions under which uniformly distributed live loads may be reduced for structural components such as slabs and beams. It specifies limitations based on live load thresholds and provides equations for calculating permissible reductions. Applies to building owners involved in structural design and load calculations.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1607.11.2 Alternative uniform live load reduction.

BC § 1607.11.2

As an alternative to Section 1607.11.1 and subject to the limitations of Table 1607.1, uniformly distributed live loads are permitted to be reduced in accordance with the following provisions. Such reductions shall apply to slab systems, beams, girders, columns, piers, walls and foundations.

1.A reduction shall not be permitted where the live load exceeds 100 psf (4.79 kN/m 2 ) except that the design live load for members supporting two or more floors is permitted to be reduced by a maximum of 20 percent. Exception: For uses other than storage, where approved, additional live load reductions shall be permitted where shown by the registered design professional that a rational approach has been used and that such reductions are warranted.

2.A reduction shall not be permitted in passenger vehicle parking garages except that the live loads for members supporting two or more floors are permitted to be reduced by a maximum of 20 percent.

3.For live loads not exceeding 100 psf (4.79 kN/m 2 ), the design live load for any structural member supporting 150 square feet (13.94 m 2 ) or more is permitted to be reduced in accordance with Equation 16-31.

4.For one-way slabs, the area, A, for use in Equation 16-31 shall not exceed the product of the slab span and a width normal to the span of 0.5 times the slab span. R = 0.08 (A - 150) (Equation 16-31) For SI: R = 0.861 (A - 13.94) Such reduction shall not exceed the smallest of: 1. 40 percent for horizontal members; 2. 60 percent for vertical members; or 3. R as determined by the following equation. R = 23.1 (1 + D / Lo ) (Equation 16-32) where: A = Area of floor or roof supported by the member, square feet (m 2 ). D = Dead load per square foot (m 2 ) of area supported. Lo = Unreduced live load per square foot (m 2 ) of area supported. R = Reduction in percent.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1607.11.2?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters