This section outlines the requirements for safe areas in assembly spaces, including capacity, separation from assembly spaces by fire barriers, and specifications for dimensions and occupant load. Safe areas must accommodate all occupants and meet specific fire safety standards. Applies to building owners managing assembly spaces.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1029.19.3 Safe areas.

BC § 1029.19.3

The capacity of exits from safe areas shall be provided for all occupants of the safe area. Safe areas shall comply with the following requirements: 1. When provided to serve Class 1 or 2 exit access doorways, safe areas shall be separated from assembly spaces by fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both, each having a 2-hour fire-resistance rating. Such safe areas shall serve as transition areas in the line and direction of exit travel. They shall serve for normal entry to the assembly space and may be used as corridors, lobbies or lounges.

2.No room or space classified in Occupancy Group H, S-1, F-1 or F-2 shall open upon a safe area.

3.Safe areas shall be at a level not more than 6 feet (1828.8 mm) above or below the level at which egress is made from the assembly space.

4.Ventilating systems for safe areas shall not be connected to systems serving any other spaces, unless separated from such systems by fire/smoke dampers actuated by smoke detectors.

5.Collecting safe areas. Places of assembly having more than one assembly space may have a collecting safe area that receives the occupant load discharged into it by other safe areas. Collecting safe areas shall be located within 6 feet (1828.8 mm) above or below the assembly space nearest to grade.

6.Occupant load. The occupant load of a safe area shall be the aggregate occupant load of all exit access doorways discharging directly into it. The occupant load of a collecting safe area shall be the aggregate occupant load of all exit access doorways discharging directly into it, plus 50 percent of the occupant load of other safe areas discharging into it.

7.Dimensions. The clear unobstructed floor area of each safe area shall be sufficient to accommodate the total occupant load of the safe area on the basis of 3 square feet (0.28 m 2 ) per person, not including space occupied by furniture or equipment. The minimum dimension of such unobstructed space shall be 8 feet (2438.4 mm). The width of the unobstructed space shall be measured at right angles to the direction of travel to an exit and shall not be less than required for the occupant load. The height of safe areas shall be at least 8 feet (2438.4 mm) at all points.

8.Safe areas near grade. When a safe area provides egress to an open exterior space, either directly or through a vestibule, the safe area need not provide the floor area required by this section when the level of discharge from the safe area to the open exterior space is not more than 4 feet (1220 mm) above or below the grade of the open exterior space.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1029.19.3?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters