This section outlines the requirements for electric locking systems on controlled egress doors in Group I-1 and I-2 occupancies, ensuring safety and accessibility for occupants while accommodating clinical needs. It specifies conditions under which these systems may be used, including the need for emergency unlocking mechanisms. Applies to building owners operating healthcare facilities with specific occupancy types.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →

1010.1.9.6 Controlled egress doors in Groups I-1 and I-2.

BC § 1010.1.9.6

Electric locking systems, including electro-mechanical locking systems and electromagnetic locking systems, shall be permitted to be locked in the means of egress in Group I-1 or I-2 occupancies where the clinical needs of persons receiving care require their containment. Controlled egress doors shall be permitted in such occupancies where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or an approved automatic smoke or heat detection system installed in accordance with Section 907, provided that the doors are installed and operate in accordance with all of the following: 1. The door locks shall unlock on actuation of the automatic sprinkler system or automatic fire detection system.

2.The door locks shall unlock on loss of power controlling the lock or lock mechanism.

3.The door locking system shall be installed to have the capability of being unlocked by a switch located at the fire command center, a nursing station or other approved location. The switch shall directly break power to the lock.

4.A building occupant shall not be required to pass through more than one door equipped with a controlled egress locking system before entering an exit.

5.The procedures for unlocking the doors shall be described and approved as part of the emergency planning and preparedness required by the New York City Fire Code.

6.All clinical staff shall have the keys, codes or other means necessary to operate the locking systems.

7.Emergency lighting shall be provided at the door.

8.The door locking system units shall be listed in accordance with UL 294. Exceptions: 1. Items 1 through 4 shall not apply to doors to areas occupied by persons who, because of clinical needs, require restraint or containment as part of the function of a psychiatric treatment area.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 1010.1.9.6?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters