(a) Scope. Pursuant to section 915.1.2 of the Building Code (BC), listed carbon monoxide (CO) detectors must be installed in buildings equipped with a fire alarm system that contain Group A-1, A-2, A-3, B or M occupancies, as defined in BC Chapter 3.

General informational summary. Not legal advice for your situation. Consult an attorney before acting on any specific matter.

Michael Nacmias - Founding PartnerMichael Sargo - Partner
From the team atNacmias Law Firm, PLLCBrooklyn-based attorneys representingproperty owners across all five boroughsMeet the team →
Effective: 11/9/2019Last amended: 1/26/2025

§ 915-01 Carbon Monoxide Detectors.

RCNY § 915-01

(a)Scope. Pursuant to section 915.1.2 of the Building Code (BC), listed carbon monoxide (CO) detectors must be installed in buildings equipped with a fire alarm system that contain Group A-1, A-2, A-3, B or M occupancies, as defined in BC Chapter 3. Such listed carbon monoxide detectors must be connected to the fire alarm system control panel and installed in accordance with the requirements of this section.

(b)Reference. See § 28-315.11 of the New York City Administrative Code (AC), and BC sections 915.1.2, 915.3, 915.4, and 915.6.

(c)Group A-1, A-2, A-3, B or M occupancies. CO detectors with built-in sounder bases meeting the requirements of BC section 915.6 and subdivision (g) of this section must be installed in the following locations: (1) Any room containing CO-producing equipment.

(2)Any interior space or area immediately adjacent to a CO-producing source, including the vertical projection of the immediate area of the floor above the CO-producing source and the immediate area of the floor below the CO-producing source.

(3)Any interior space or area immediately adjacent to an enclosed parking garage or a loading dock, including the vertical projection of the immediate area of the floor above the enclosed parking garage or loading dock and the immediate area of the floor below the enclosed parking garage or loading dock.

(4)Any parking attendant’s office or booth located within an enclosed parking garage or loading dock.

(5)As an alternative to installation as provided in paragraphs (1) through (4) of this subdivision and subject to the Department’s approval, in locations determined by a performance-based design that is in accordance with section 5.8.5.3.2 of reference standard National Fire Protection Association (“NFPA”) 720 – 2015 edition.

(d)Equipment shutdown. Activation of a CO detector located at the source of CO-producing equipment must shut down that pursuant to BC section 915.3.1. Exception: This provision does not apply where the source is a generator.

(e)Installation requirements. CO detectors must be installed in accordance with NFPA 720 – 2015 edition, as modified for New York City by 1 RCNY § 3616-08.

(f)Fire alarm control units. CO detectors must be connected and monitored at the fire alarm control panel or Fire Command Center. Pursuant to the provisions of section 23.8.2.2 of NFPA 72 – 2016, if there is insufficient space in the existing fire alarm control panel to monitor the carbon monoxide detectors, a new separate fire alarm control panel may be installed. However, the new fire alarm control panel must function as if it were part of the original building fire alarm system, and such dedicated function fire alarm control panel must be interconnected with the building’s master fire alarm control panel or Fire Command Station.

(g)Visual Notification Appliance Installation Requirements. In Group A-1, A-2, A-3, B or M occupancies where CO detection is required, visual notification appliances required by Section 6.4.1.1 of NFPA 720 – 2015, must be installed in accordance with this subdivision.

(1)Visual notification appliance devices must be installed within 10 feet of any CO detector.

Common Questions

Our team

Meet the people you will work with

Free case review

Have a matter that touches § 915-01?

Free 15-minute case review with the attorney handling your matter. Same-day response during business hours across all five boroughs — OATH hearings, Housing Court, and real estate closings.

Or email us

[email protected]

An attorney reads every message.

  • Same-day response

    During business hours

  • Direct attorney access

    Same lawyer from intake to close

  • Flat-fee pricing

    On most OATH and closing matters