§ 103-04 Periodic Inspection of Exterior Walls and Appurtenances of Buildings.
RCNY § 103-04
(a)Definitions. For the purposes of this section, the following terms have the following meanings. Acceptable report. A technical examination report filed by a Qualified Exterior Wall Inspector that meets the requirements of the Administrative Code and this rule as determined and approved by the Department. Amended report. A technical examination report filed by a Qualified Exterior Wall Inspector who certifies that the unsafe conditions reported in the initial report have been repaired and that no unsafe conditions exist at the building. Appurtenance. An exterior wall element including, but not limited to, fire escapes, exterior fixtures, ladders to rooftops, flagpoles, signs, parapets, railings, copings, guard rails, window frames (including hardware and lites), balcony and terrace enclosures, including greenhouses or solariums, window guards, window air conditioners, flower boxes, satellite dishes, antennae, cell phone towers, and any equipment attached to or protruding from the facade. Cavity wall construction. An exterior wall system consisting of an exterior veneer with a backup wall whereby the exterior veneer relies on a grid of metal ties to the backup wall for lateral stability. The two layers of wall are separated by an air cavity which may or may not be filled with insulation. Critical examination. An examination conducted to review the exterior of a building and all parts thereof to determine whether the exterior walls (facades) and the appurtenances are either safe, unsafe, or safe with a repair and maintenance program (SWARMP) and whether, in the judgment of a Qualified Exterior Wall Inspector, they require remedial work. Filed report. A report shall be deemed filed with the Department when it has been received by the Department. The filed report must be completed in accordance with the provisions of paragraph (3) of subdivision (c) of this section. Filing window. The two-year period during which a report for a particular building may be filed without penalty. Public right-of-way. A public street, avenue, sidewalk, roadway or any other public place or public way. Qualified Exterior Wall Inspector (hereinafter "QEWI"). A qualified exterior wall inspector as defined in 1 RCNY § 101-07. Report filing cycle. The five-year time interval established by the Commissioner for the filing of each successive report for each successive critical examination of every building subject to the requirements of Article 302 of Title 28 of the Administrative Code. Safe condition. A condition of a building wall, any appurtenances thereto or any part thereof not requiring repair or maintenance to sustain the structural integrity of the exterior of the building and that will not become unsafe during the next five years. Safe with a repair and maintenance program (hereinafter "SWARMP"). A condition of a building wall, any appurtenances thereto or any part thereof that is safe at the time of inspection, but requires repairs or maintenance during the next five years, but not less than one year, in order to prevent its deterioration into an unsafe condition during that five-year period. Staggered inspection cycle. The separate time intervals for filing reports of critical examinations as determined by the last digit of the building's block number, beginning February 21, 2010, and continuing thereafter for each subsequent report filing cycle. Subsequent report. A technical examination report that is filed by a QEWI after an acceptable report in order to change the status of the building for that report filing cycle to reflect changed conditions or the recommended time frame for repairs of SWARMP or unsafe conditions. Unsafe condition. A condition of a building wall, any appurtenances thereto, or any part thereof that is hazardous to persons or property and requires repair within one (1) year of completion of critical examinations. In addition, any condition that was reported as SWARMP in a previous report and that is not corrected at the time of the current inspection must be reported as an unsafe condition.
(b)Responsibilities of qualified exterior wall inspectors.
(1)A QEWI must conduct critical examinations and file reports in accordance with this section and Article 302 of Title 28 of the Administrative Code.
(2)A QEWI must maintain records of inspections and tests for at least six years and must make such records available to the Department upon request.
(3)A QEWI must maintain insurance coverage as set forth in paragraph (7) of subdivision (b) of 1 RCNY § 101-07. Copies of such insurance policies must be made available to the Department upon request.
(c)Critical examinations.
(i)Before any exterior wall for any building is critically examined, the QEWI retained by or on behalf of the owner of the building must carefully review the most recent report and any available previous reports. The Department will maintain a file of such reports submitted in conformance with Article 302 of Title 28 of the New York City Administrative Code, and furnish copies upon payment of fees set forth in the rules of the Department.
(ii)Examination of a building's exterior walls and appurtenances thereof pursuant to § 28-302.2 of the Administrative Code must be performed by or under the direct supervision of a QEWI retained by the owner of the building or his or her representative.
(iii)The QEWI must design an inspection program for the specific building to be inspected, which must include, but not be limited to, the methods to be employed in the examination. The inspection program shall be based on considerations of the type of construction of the building's envelope, age of the material components, the facade's specific exposure to environmental conditions and the presence of specific details and appurtenances. Consideration shall be given to the facade's history of maintenance and repairs as described in previous reports and submittals to the Department. Architects, engineers, individuals with a bachelor's degree in architecture or engineering and three (3) years of relevant FISP inspection experience, or individuals with five (5) years of relevant FISP inspection experience working under the QEWI's direct supervision, may be delegated to perform selected inspection tasks.
(iv)The methods used to examine the building must permit a complete inspection of same. Except as herein required, the use of a scaffold or other observation platform is preferred, but the QEWI may use other methods of inspection as he/she deems appropriate. Physical examinations from scaffolding or other observation platform ("close-up inspections") must be performed at intervals of not more than 60'-0", with the minimum number of physical examinations per total length of facade elevation noted in the table below. If the building does not front a public right-of-way, physical examinations are to be performed at a representative sample of the facade elevations with a minimum of one examination per building. All physical examinations shall occur along a path from grade to top of an exterior wall fronting each public right-of-way, using at least one scaffold drop or other observation platform configuration, including all exterior wall setbacks. The QEWI shall determine the most deleterious locations and perform physical examinations at those locations. The use of drones, high resolution photography, non-destructive testing, or other similar methods does not eliminate the requirements for close-up inspections. Length of Facade Elevation Fronting Public Right-of-Way (L)Minimum # of Physical ExaminationsLength of Facade Elevation Fronting Public Right-of-Way (L)Minimum # of Physical ExaminationsL < 60'-0"160'-0" ≤ L < 120'-0"2120'-0" ≤ L < 180'-0"3180'-0" ≤ L < 240'-0"4240'-0" ≤ L < 300'-0"5300'-0" ≤ L < 360'-0"6For every additional 60'-0" of length of facade, one additional close-up inspection is required.
(v)The known history of the building, the nature of the materials used and the conditions observed will dictate the extent of the critical examination. The QEWI must apply a professional standard of care to assess the building's condition and the individual building systems that comprise the facades, including splitting or fracturing of terra cotta on buildings, cracking of masonry and brick work in brick faced buildings, mortar and other joint materials, loosening or corrosion of metal anchors and supports, water entry or flow within cavities, mineral build-up, coping materials, movement of lintel/shelf angles, and must ascertain the cause of these and such other conditions detected. The QEWI must order any special or additional inspections and/or tests, including sounding procedures, that may be required to support investigations and to determine the causes of any defects. Starting with the ninth cycle, probes must be performed on all cavity wall construction, and, at a minimum, during every subsequent odd-numbered cycle. The QEWI shall determine the location of the probes, which shall be in areas not previously renovated. At a minimum, a single probe must be completed along each required close-up inspection interval. The QEWI must ensure that the number and size of the probes are sufficient to report the presence, condition, and spacing of wall ties. The removal of portions of the facade in order to facilitate the performance of tests may require a permit from the Landmarks Preservation Commission. Exceptions: The requirement for probes may be waived in the following cases: 1. When a repair campaign addressing cavity wall ties has been completed within ten (10) years of the filing deadline and the owner or QEWI provides proof of such repair including, but not limited to, photographs, special inspection reports, and construction documents, which must be submitted and found acceptable by the Department.
2.When the first Temporary Certificate of Occupancy or Certificate of Occupancy for a new building was issued within ten (10) years of the filing deadline and the owner or QEWI provides evidence of tie installation including, but not limited to, photographs, special inspection reports, and construction documents, which must be submitted and found acceptable by the Department.
3.Where a QEWI proposes an alternate method of determining tie condition and spacing, which must be submitted and found acceptable by the Department.
(vi)Photographs must be taken and/or sketches made during the course of the Critical Examination to properly document the location of all conditions observed that are either unsafe or SWARMP.
(vii)Upon discovery of any unsafe condition, the QEWI must immediately notify the Department and the owner of the building. The QEWI must identify the location of any unsafe condition, advise the owner on the appropriate protective measures to be taken, and include the recommended type and location of public protection in the notification to the Department.
(viii)Completion of a critical examination means that the QEWI has conducted a final physical inspection to determine that the building conditions as described in the report are consistent with the actual conditions. Such final inspection must, at a minimum, include an actual visual examination and a walk around with binoculars or other inspectorial equipment. A drive-by inspection is not acceptable.
(4)Report filing requirements.
(ix)A report may not be filed more than one (1) year after completion of the close-up inspection.
(x)If the report is not acceptable and is rejected by the Department, a revised report must be filed within forty-five (45) days of the date of the Department's rejection, after which the original file date will no longer be valid. If the report is not acceptable after two (2) rejections, a new initial filing fee as specified in the rules of the Department is required. Failure to submit a revised report addressing the Department's objections within one (1) year of the initial filing requires a new critical examination, including a new close-up inspection.
(xi)A subsequent report indicating revised conditions may be filed within a five-year report filing cycle to change a building's filing status for that cycle.
(5)Unsafe conditions.
(6)Conditions that are safe with a repair and maintenance program (SWARMP).
(d)Civil penalties.
(e)Full or partial penalty waivers; eligibility and evidentiary requirements. Owners may request a full or partial waiver of penalties assessed for violation of Article 302 of Title 28 of the Administrative Code, the New York City Building Code and/or rules enforced by the Department. Requests must be made through the Department’s website, submitted with the filing fee, and must meet eligibility and evidentiary requirements as follows: (1) Owner status.
(f)Posting of conditions certificate. A conditions certificate issued by the Commissioner must be posted in a frame with a transparent cover in the lobby or vestibule of the subject building within thirty (30) days of issuance. The certificate must indicate the most recent condition of the building's exterior walls and appurtenances. (Amended City Record 1/21/2020, eff. 2/20/2020; amended City Record 10/13/2021, eff. 11/12/2021; amended City Record 1/2/2026, eff. 2/1/2026)